Siemens RDG160T Manual, Specifications and Replacement Options
The Siemens RDG160T is a wall-mounted room thermostat with LCD for fan coil units, chilled or heated ceilings and compressor-based DX equipment. It runs on AC/DC 24 V and drives valves and ECM fans with DC 0…10 V signals, or uses relay outputs for On/Off control and 3-speed fans. The full manual is below, along with the key specifications and commissioning notes.
Download the RDG160T Manual
Download the Siemens RDG160T manual (PDF)
This is the Siemens data sheet for the RDG1.. range of wall-mounted room thermostats with LCD (document CE1N3181en, dated 2015-07-29). It covers the RDG160T alongside the RDG100, RDG100T, RDG100T/H, RDG110, RDG110U and RDG160TU, so check that you are reading the RDG160T rows and diagrams.
RDG160T Specifications
| Specification | Value |
|---|---|
| Siemens stock number | S55770-T343 |
| Operating voltage | SELV AC/DC 24 V, 50/60 Hz (for DC 24 V, G = + and G0 = –) |
| Power consumption | Max. 2 VA / 1 W |
| Relay outputs Q1, Q2, Q3 | AC 24…230 V via terminal L. Fan rating 5 mA…5(4) A. Max. total load Q1+Q2(+Q3) 5 A for actuator use |
| DC 0…10 V outputs | Y10 and Y20 for valve actuators (max. ±1 mA). Y50 for ECM fan (max. ±5 mA) |
| Fan control | 1-speed, 3-speed or DC 0…10 V ECM fan |
| Inputs | X1 and X2 multifunctional (NTC 3k at 25 °C sensor or digital contact), D1 digital input. Sensor cable max. 80 m |
| Built-in sensor | Measuring range 0…49 °C, accuracy < ±0.5 K at 25 °C, calibration range ±3.0 K |
| Comfort setpoint | 21 °C factory setting, adjustable 5…40 °C |
| Time program | 7-day program with 8 programmable timers, infrared receiver for the IRA211 remote (ordered separately) |
| Operating conditions | 0…50 °C, < 95% r.h. Housing IP30 to EN 60529, safety class II |
| Weight and dimensions | 0.32 kg, 128 x 93 mm |
Setup and Commissioning Notes
The data sheet does not list error codes, but it does set out the checks that solve most commissioning problems. These are the points worth getting right on site.
Set the DIP switches before fitting the front
Select the application with the DIP switches at the rear of the thermostat before you fit the front housing to the mounting plate. On power-up the thermostat resets and all LCD segments flash, which shows the reset was correct. After about 3 seconds it is ready for commissioning.
Check the control sequence (P01)
If the unit only cools or only heats, check parameter P01. The factory setting for 2-pipe applications is cooling only, and heating and cooling for 4-pipe applications.
Displayed temperature does not match the room
Recalibrate the built-in sensor with parameter P05 if the temperature on the display does not match the measured room temperature. The calibration range is ±3.0 K.
Wiring and protection checks
There is no internal fuse and no internal line protection for the outputs, so the supply needs a circuit breaker of no more than 10 A. Fans must not be connected in parallel: connect one fan directly and use one relay per speed for any additional fans. If AC 230 V is connected to terminal L, use only valve actuators rated for AC 230 V.
Fault and condensation symbols
The display has a fault symbol and a condensation symbol (shown when a dewpoint sensor is active). The X1, X2 and D1 inputs can be set as a fault input or dewpoint sensor input via parameters P38, P40 and P42, so check which inputs are configured and what is wired to them when either symbol appears.
Buy the RDG160T
- Siemens RDG160T room controller: the exact model covered by this manual, with 7-day timeswitch, 3-speed or ECM fan control and DC 0…10 V outputs. Check the product page for current availability.
- Stand-alone controllers and thermostats: our full range of room thermostats and stand-alone controllers.
- Siemens range: all Siemens products we list, including other RDG and RDF thermostats.
Choosing between fan coil thermostats? Our guide to choosing a fan coil unit room controller covers the main selection points.
Need help identifying a replacement?
Send us the model number from the existing thermostat and details of the fan coil or DX unit it controls, and we can confirm whether the RDG160T suits your application.
Contact Controls Traders and our team will help you spec it.
Frequently Asked Questions
Where can I download the Siemens RDG160T manual?
You can download the Siemens RDG1.. data sheet that covers the RDG160T from this page: RDG160T manual (PDF). It is Siemens document CE1N3181en dated 2015-07-29 and includes the applications, technical data, terminal layout, connection diagrams and dimensions.
What are the Siemens RDG160T specifications?
The RDG160T runs on SELV AC/DC 24 V and draws a maximum of 2 VA / 1 W. It has three relay outputs (Q1 to Q3, AC 24…230 V), two DC 0…10 V actuator outputs (Y10, Y20) and a DC 0…10 V ECM fan output (Y50). The built-in sensor measures 0…49 °C with an accuracy better than ±0.5 K at 25 °C, and the housing is rated IP30.
How do I wire the Siemens RDG160T?
Connect the 24 V supply to G and G0 (for DC 24 V, G is positive and G0 negative). Terminal L supplies the relay outputs Q1 to Q3 at AC 24…230 V. Y10 and Y20 drive DC 0…10 V valve actuators, Y50 drives an ECM fan, X1 and X2 take a sensor or contact against M, and D1 takes a contact against GND. The supply needs a circuit breaker of no more than 10 A, as there is no internal fuse. Follow the mounting instructions supplied with the thermostat.
What applications does the RDG160T support?
It is set up with DIP switches for 2-pipe and 4-pipe fan coil units (including 2-pipe with electric heater or radiator, and 2-stage), chilled or heated ceilings, and 1-stage or 2-stage compressors in DX-type equipment.
What is the difference between the RDG160T and the RDG160TU?
Both are 24 V thermostats with a timer and DC (or On/Off) outputs for valve and fan. The RDG160TU is the UL certified version: its relay outputs run at AC 24 V class 2 through terminal C instead of AC 24…230 V through terminal L, and it has a wizard to choose °C or °F at start-up.
Is the Siemens RDG160T still available?
The RDG160T is listed in our catalogue under SKU RDG160T. Check the RDG160T product page for current availability, or contact our team if you need help sourcing one.
Leave a comment
Popular Posts
Siemens RDG160T Manual, Specifications and Replacement Options
Honeywell ML7984A4009 Manual, Specifications and Replacement Options
Dwyer Magnesense AT-MSX Manual, Specifications and Replacement Options