Dual-Technology Occupancy Sensors: A Practical Guide to the Leviton 24V Range
A dual-technology occupancy sensor detects people using two methods at once, typically passive infrared (PIR) for body heat and ultrasonic for small movements. Because it can confirm occupancy with one technology and hold the space on with the other, it switches far less often by mistake than a PIR-only sensor. The Leviton 24V range adds an isolated relay, so the same sensor can switch lighting and tell an HVAC or BMS controller whether a room is occupied.
This guide explains how dual-technology detection works, compares the two Leviton models we stock, and covers how to wire them into lighting and HVAC control on Australian projects.
- Best for: offices, meeting rooms, classrooms and amenities where people sit still for long periods.
- Leviton models: OSC20-RMW ceiling-mount sensor and OSW12-RMW wall-mount sensor.
- Supply: 24 VAC/VDC, Class 2 low voltage.
- Outputs: a 24 VDC control signal plus a 1A at 30 VAC/VDC isolated relay for a BMS or controller input.
What Is a Dual-Technology Occupancy Sensor?
An occupancy sensor turns a load on when a space is occupied and off after a set time once it is empty. Single-technology sensors rely on one detection method, and each method has a blind spot. Dual-technology sensors put two methods in one housing so each covers the other's weakness.
Passive infrared (PIR)
PIR sensors watch for changes in infrared heat across a set of zones created by a segmented lens. A person walking through the zones produces a strong, clear signal, so PIR is reliable for major motion and rarely triggers falsely. The limitation is that PIR needs line of sight and visible movement. Someone sitting at a desk behind a partition, or reading quietly, may not register.
Ultrasonic
Ultrasonic sensors emit a high-frequency sound (32 kHz on the Leviton OSC20) and measure changes in the reflected signal. They detect small movements such as typing or turning a page, and the sound fills the room so partitions and furniture matter less. The trade-off is sensitivity to things that are not people, including strong air movement from diffusers.
How the two combine
In the usual dual-technology logic, the sensor needs to see occupancy before switching on, then either technology can hold the load on. PIR provides a confident trigger when someone walks in, and ultrasonic keeps the room on while they sit still. Leviton's RMW sensors also use a microprocessor that adjusts sensitivity and time delay over time based on how the space is actually used, and keeps those learned settings through a power outage.
PIR vs Ultrasonic vs Dual-Technology
| Feature | PIR | Ultrasonic | Dual-technology |
|---|---|---|---|
| Detection method | Body heat moving across lens zones | Changes in reflected high-frequency sound | Both, in one housing |
| Minor motion (typing, reading) | Limited | Good | Good |
| Needs line of sight | Yes | No | Only to trigger on |
| False-on risk | Low | Higher near airflow or vibration | Low |
| False-off risk | Higher with still occupants | Low | Lowest |
| Typical spaces | Corridors, store rooms, small rooms | Toilets with cubicles, partitioned areas | Offices, meeting rooms, classrooms, open plan |
The Leviton 24V Range: OSC20-RMW vs OSW12-RMW
Controls Traders stocks two models from Leviton's low voltage multi-technology range. Both share the same electrical design. The difference is where they mount and the shape of the area they cover. You can see both on our Leviton range page.
| Specification | OSC20-RMW (ceiling) | OSW12-RMW (wall or corner) |
|---|---|---|
| Technology | PIR + ultrasonic | PIR + ultrasonic |
| Mounting | Ceiling | Wall or corner |
| Coverage pattern | 360 degrees | 110 degree lens |
| Maximum coverage | About 186 m² (2,000 sq ft) | About 111 m² (1,200 sq ft) |
| Mounting height | 2.4 to 3.7 m with the standard lens | 2.4 to 3.0 m |
| Supply | 24 VAC/VDC, Class 2 | 24 VAC/VDC, Class 2 |
| Current draw | 32 mA DC, 50 mA AC | 24 mA DC, 45 mA AC |
| Outputs | 24 VDC control signal + isolated relay, 1A at 30 VAC/VDC | 24 VDC control signal + isolated relay, 1A at 30 VAC/VDC |
| Time delay | 30 s to 30 min, self-adjusting | 30 s to 30 min, self-adjusting |
| Operating conditions | 0 to 40°C, 0 to 95% RH non-condensing | 0 to 40°C, 0 to 95% RH non-condensing |
Leviton certifies both sensors for use under US energy codes such as ASHRAE 90.1 and California Title 24. Those codes do not apply in Australia, but the certification is a useful indicator of build quality. For Australian projects, confirm what your NCC Section J and lighting design require with the project's services engineer.
Ceiling or Wall Mount: Which Should You Choose?
The Leviton OSC20-RMW ceiling sensor sees the room from above, so it handles open spaces and rooms where people face different directions. The OSW12-RMW wall-mount sensor looks across the room from one side, which suits smaller rooms where the occupants face a known direction. For the OSW12-RMW, Leviton rates the large-motion range at about 20.7 m and the small-motion range at about 9.4 m.
- Open-plan office bay: OSC20-RMW, centred over the workstations. Large bays may need more than one sensor, wired in parallel to the same input.
- Meeting room or boardroom: either works. Use the OSW12-RMW in a corner facing the table if the ceiling is crowded with diffusers and lights.
- Private office: OSW12-RMW in the corner nearest the door, angled towards the desk.
- Amenities with cubicles: OSC20-RMW, where ultrasonic detection over partitions matters more than line of sight.
- High ceilings: the OSC20's standard lens suits 2.4 to 3.7 m. Leviton specifies a mid-range lens for 3.7 to 6.1 m, so check which lens is fitted before installing in warehouses or atriums.
Using the Isolated Relay for HVAC Control
Most occupancy sensor guides stop at lighting. On HVAC projects the isolated relay is the more valuable feature. It gives a voltage-free contact that is completely separate from the sensor's own power, so it can go straight into a controller input without any risk of feeding the sensor supply back into the BMS.
Typical HVAC applications
- Occupied and unoccupied setpoints: wire the relay to a digital input on the zone controller. When the room is empty the controller widens the heating and cooling setpoints, then returns to comfort settings when someone walks in.
- VAV minimum airflow setback: on a VAV box serving a meeting room, an unoccupied signal can drop the minimum airflow to its unoccupied value and close the reheat valve. This saves fan energy and reheat without affecting comfort while the room is in use.
- Fan coil unit enable: a stand-alone controller or thermostat with an occupancy input can stop the fan coil, or switch it to economy mode, in hotel rooms, offices and classrooms.
- One sensor for two systems: the 24 VDC control output can drive the lighting relay while the isolated relay reports occupancy to the BMS. That saves a second sensor and keeps lighting and air conditioning in step.
Things to check before wiring
- The relay is rated 1A at 30 VAC/VDC. Use it for controller inputs and low voltage relay coils only. It must not switch 230V lighting or plant directly.
- Confirm whether the controller input expects a normally open or normally closed contact, and configure the input or the sensor wiring to match.
- Set a longer time delay for HVAC than for lighting. Plant should not start and stop every time someone steps out for a few minutes.
- Check the BMS logic has a minimum occupied time and a sensible fallback mode if the sensor input fails.
Wiring and Power Supply
The Leviton RMW sensors use a three-wire Class 2 low voltage connection with a twist-lock attachment to the mounting plate. They need a 24 VAC or 24 VDC supply, and several sensors can share one supply provided the total current draw stays within its rating.
On Australian HVAC jobs the supply usually comes from one of two places:
- The controller's 24V output: many BMS, VAV and fan coil controllers provide a 24V auxiliary supply. Check that it has enough spare capacity for the sensor's 45 to 50 mA AC draw.
- A dedicated control transformer: a 230V to 24VAC transformer in the control panel can supply several sensors plus other field devices.
For lighting, the sensor's 24 VDC output normally drives the coil of a relay or contactor that switches the lighting circuit, or feeds an input on a lighting control system. Any work on mains-voltage circuits must be carried out by a licensed electrician.
Installation Tips for Reliable Detection
- Keep clear of supply air: mount the sensor well away from supply diffusers and return grilles so airflow is not read as motion. A common rule of thumb is at least 1.2 m.
- Avoid seeing through doorways: aim wall sensors away from open doors and corridors so passing foot traffic does not switch the room on.
- Use walk-through mode where it helps: Leviton's walk-through feature shortens the time delay to about 2.5 minutes when someone only passes through briefly, which suits store rooms and copy rooms.
- Test before handover: use the sensor's test mode to walk the coverage area, then confirm the relay state changes at the controller or BMS front end.
- Let it learn: the self-adjusting function needs time in normal use. Avoid re-tuning sensitivity in the first week unless there is a clear fault.
Browse our full light and motion sensors category for other occupancy sensing options.
Need help choosing the right occupancy sensor?
Controls Traders stocks the Leviton OSC20-RMW and OSW12-RMW in Adelaide, along with the transformers and controllers that pair with them. Tell us about the space and the system it needs to talk to, and we will help you pick the right model.
Contact Controls Traders and our team will help you spec it.
Frequently Asked Questions
What does dual-technology mean in an occupancy sensor?
A dual-technology (or multi-technology) occupancy sensor combines two detection methods in one housing, usually passive infrared (PIR) and ultrasonic. PIR detects the heat of a moving body in its line of sight, while ultrasonic detects small movements by measuring changes in reflected high-frequency sound. Using both reduces false switching compared with either technology on its own.
Is a dual-technology sensor better than a PIR sensor?
For most occupied rooms, yes. A PIR-only sensor can switch lights or air conditioning off while people sit still at a desk or around a meeting table, because it needs a clear line of sight and visible movement. Adding ultrasonic detection lets the sensor pick up small movements such as typing, so the space stays on while it is in use. PIR-only sensors still suit corridors and small rooms with obvious movement.
What is the difference between the Leviton OSC20-RMW and OSW12-RMW?
Both are 24V multi-technology sensors with a 1A isolated relay. The OSC20-RMW mounts on the ceiling, has a 360 degree pattern and covers up to about 186 square metres (2,000 sq ft). The OSW12-RMW mounts on a wall or in a corner, has a 110 degree lens and covers up to about 111 square metres (1,200 sq ft). Choose the ceiling model for open areas and the wall model for rooms where the occupants face one direction.
Can an occupancy sensor control HVAC as well as lighting?
Yes. The isolated relay on the Leviton RMW models gives a dry contact that can be wired to a digital input on a BMS controller, VAV controller or fan coil controller. The controller can then switch the zone between occupied and unoccupied modes, for example by widening the temperature setpoints or reducing VAV minimum airflow when the room is empty.
What voltage do Leviton RMW occupancy sensors need?
The OSC20-RMW and OSW12-RMW are low voltage sensors designed for a Class 2, 24 VAC or 24 VDC supply. They do not connect to 230V mains. In an Australian HVAC installation the supply usually comes from a 24VAC control transformer or the controller's own 24V output, with any mains switching done by a separate relay or contactor installed by a licensed electrician.
What time delay should I set on an occupancy sensor?
The Leviton RMW sensors have a time delay range of 30 seconds to 30 minutes and can self-adjust over time. For HVAC control a longer delay, often 15 to 30 minutes, avoids short cycling plant when people step out briefly. For lighting in meeting rooms and offices, 10 to 20 minutes is a common starting point. Short delays are best kept for testing and low-traffic spaces.
Do air conditioning diffusers affect ultrasonic occupancy sensors?
They can. Ultrasonic detection responds to air movement, so a sensor mounted close to a supply air diffuser may see the airflow as motion and hold the room on. Mount ultrasonic and dual-technology sensors well away from supply diffusers and return grilles. A common rule of thumb is at least 1.2 metres, and further for high-velocity outlets.